Computer-Use Agent Taxonomy中文
R07.07.02.02 · TASK CLASS

HMI/SCADA screen engineering

Build operator screens and bind tags and alarms.

20 project-authored proposals · taxonomy v1.1 · 0 new benchmark runs. Verifiers and partial-credit rules below are designs, not executed results.

Typical applications
Ignition · WinCC · FactoryTalk View
Class GUI-need label
G3 · GUI-only

Task proposals · 20

Expand to inspect the complete original wording and proposed checks. Original proposal text remains English in both interfaces.

R07.07.02.02-T01 Build a Perspective tank view with level binding, high alarm and a setpoint writer

Original instruction

In Ignition 8.1 Designer (sandbox gateway, project 'WaterPlant') create Perspective view Tanks/Tank1: a cylindrical tank graphic with fill bound to [default]Tank1/Level (0-100%), numeric label with 1 decimal, a red indicator when the tag's alarm 'HighLevel' (>90%) is active, and a numeric entry + 'Apply' button that writes Tank1/SP (range 0-95). Configure the alarm on the tag too.

Platforms
win · Windows mac · macOS lin · Linux
Applications
Ignition
Interfaces
desk · Desktop GUI
GUI need · task setting
G2 · GUI-essential
GUI need · ordinary access
G2 · GUI-essential
Interaction primitives
drag · Drag & drop click · Point & click type · Text & forms
Work product
WP08 · App/system state
Conditions
licensed · Licensed pro app
Proposed difficulty
3 / 5

Proposed verifier

Grader opens a Perspective session (Playwright) after forcing Level to 50/92%: fill height and label correct, indicator red only >90; writes SP=70 via UI → tag 70, SP=99 rejected. Tag config JSON has HighLevel alarm setpoint 90. Designer Script Console, gateway API tokens and file access are withheld from the agent; the gateway audit log must show edits came from a Designer session (not file pushes).

Proposed partial credit

30% level binding; 20% alarm config & indicator; 35% setpoint write with limits; 15% layout present

R07.07.02.02-T02 Configure an alarm pipeline that emails on High priority only

Original instruction

On the sandbox Ignition gateway create alarm notification profile 'SMTP-Sandbox' (host mailhog:1025), an on-call roster 'Shift-A' with 2 users, and pipeline 'HighOnly' that sends email for alarms with priority High or Critical, waits 5 min and escalates once if unacknowledged. Assign the pipeline to the 6 alarms in folder [default]Pumps.

Platforms
win · Windows mac · macOS lin · Linux
Applications
Ignition
Interfaces
brow · Browser desk · Desktop GUI
GUI need · task setting
G2 · GUI-essential
GUI need · ordinary access
G2 · GUI-essential
Interaction primitives
drag · Drag & drop click · Point & click type · Text & forms
Work product
WP08 · App/system state
Conditions
licensed · Licensed pro app
Proposed difficulty
3 / 5

Proposed verifier

Grader triggers one Low and one High alarm: MailHog receives only the High email to Shift-A users; after 5 min unacked a second email; pipeline JSON has filter/delay/escalation blocks; 6 alarms reference pipeline. Designer Script Console, gateway API tokens and gateway file access are withheld from the agent; resources must be saved from a Designer session, and the gateway audit log records the actor.

Proposed partial credit

20% notification profile; 15% roster; 40% pipeline logic; 25% alarms assigned

R07.07.02.02-T03 Add a 24-hour trend of three historian tags with specified pen colors

Original instruction

In Ignition Perspective view Overview/Trends add a Power Chart showing the last 24 h of [default]Boiler/Temp, Boiler/Pressure (second axis) and Boiler/Flow from the 'Historian' provider, pens colored #D62728, #1F77B4, #2CA02C, with axis titles and units.

Platforms
win · Windows mac · macOS lin · Linux
Applications
Ignition
Interfaces
desk · Desktop GUI
GUI need · task setting
G2 · GUI-essential
GUI need · ordinary access
G2 · GUI-essential
Interaction primitives
drag · Drag & drop click · Point & click type · Text & forms
Work product
WP08 · App/system state
Conditions
licensed · Licensed pro app
Proposed difficulty
2 / 5

Proposed verifier

view.json: chart pens for 3 tag paths with colors; pressure on secondary axis; time range 24 h; session screenshot shows 3 colored series (pixel color check). Designer Script Console, gateway API tokens and gateway file access are withheld from the agent; resources must be saved from a Designer session, and the gateway audit log records the actor.

Proposed partial credit

40% pens & tags; 20% colors; 20% axes; 20% time range

R07.07.02.02-T04 Create a pump UDT and an indirectly bound template for six pumps

Original instruction

In Ignition Designer create UDT 'Pump' (parameters PLCPath, Area; members Run, Fault, Speed, Hours, Start/Stop commands mapped via OPC to the simulator device 'PLC1'), instantiate P101-P106 per input/pumps.csv, and a Vision template 'PumpTile' with a UDT-typed parameter so each tile shows status color, speed and Start/Stop buttons. Place 6 tiles on window 'Pumps'.

Platforms
win · Windows mac · macOS lin · Linux
Applications
Ignition
Interfaces
desk · Desktop GUI
GUI need · task setting
G2 · GUI-essential
GUI need · ordinary access
G2 · GUI-essential
Interaction primitives
drag · Drag & drop click · Point & click type · Text & forms
Work product
WP08 · App/system state
Conditions
licensed · Licensed pro app
Proposed difficulty
4 / 5

Proposed verifier

Tag JSON: UDT with params/members; 6 instances with correct OPC item paths; template uses indirect binding (no hard-coded paths); grader runs Vision client: toggling P104 Fault turns only its tile red; Start writes correct OPC tag. Designer Script Console, gateway API tokens and gateway file access are withheld from the agent; resources must be saved from a Designer session, and the gateway audit log records the actor.

Proposed partial credit

25% UDT definition; 20% 6 instances; 35% template binding; 20% window runtime test

R07.07.02.02-T05 Engineer a WinCC Unified mixer screen with faceplates bound to PLC tags

Original instruction

In TIA Portal V19 project fixtures/mixer_wincc.ap19 build WinCC Unified screen 'Mixer' per input/mixer_mockup.png: tank with level bar, 2 inlet valve faceplates and an agitator motor faceplate from the project library, bound to the PLC DB tags, plus temperature with limits coloring. Compile and run in WinCC Unified simulation connected to PLCSIM Advanced.

Platforms
win · Windows
Applications
WinCC
Interfaces
desk · Desktop GUI
GUI need · task setting
G3 · GUI-only
GUI need · ordinary access
G2 · GUI-essential
Interaction primitives
drag · Drag & drop click · Point & click geom · Precise geometry
Work product
WP08 · App/system state
Conditions
licensed · Licensed pro app
Proposed difficulty
4 / 5

Proposed verifier

Openness export: screen items and tag connections match tag list; grader drives PLCSIM tags and screenshots runtime (browser): level bar and colors respond; faceplate commands write PLC tags; layout matches mockup (element bbox IoU ≥0.7). TIA Portal Openness is denied to the agent (its Windows user is not in the 'Siemens TIA Openness' group; exports are grader-only), so the project must be edited in the TIA Portal UI.

Proposed partial credit

25% faceplates placed & bound; 20% level/temperature dynamics; 30% runtime command test; 25% layout match

R07.07.02.02-T06 Configure discrete and analog HMI alarms with an alarm view on a Comfort panel

Original instruction

In fixtures/pack_line.ap19 (TP900 Comfort), define 8 discrete alarms from DB 'Faults' bits and 2 analog alarms (motor temp high 80 °C, high-high 95 °C) with classes Warning/Errors, alarm texts per input/alarm_list.xlsx, and an alarm view on screen 'Alarms' with acknowledge button. Simulate with PLCSIM.

Platforms
win · Windows
Applications
WinCC
Interfaces
desk · Desktop GUI
GUI need · task setting
G3 · GUI-only
GUI need · ordinary access
CL · CLI-sufficient
Interaction primitives
click · Point & click type · Text & forms drag · Drag & drop
Work product
WP08 · App/system state
Conditions
licensed · Licensed pro app multiapp · Multi-app
Proposed difficulty
3 / 5

Proposed verifier

Openness export: 10 alarms with trigger tags/bits/limits/classes/texts per list; alarm view present; grader sets bits/temps in PLCSIM and reads HMI runtime alarm buffer (simulation API): correct alarms appear and acknowledge. TIA Portal Openness is denied to the agent (its Windows user is not in the 'Siemens TIA Openness' group; exports are grader-only), so the project must be edited in the TIA Portal UI.

Proposed partial credit

40% alarm definitions; 20% classes/texts; 25% runtime appearance; 15% alarm view & ack

R07.07.02.02-T07 Build FactoryTalk View SE motor displays with global objects and parameter files

Original instruction

In FactoryTalk View Studio SE (local station, sandbox) create global object 'MotorIcon' with parameters #1 tag base, #2 label, and a display 'Area2' with 4 motor instances via parameter files M201.par-M204.par bound to the emulated Logix controller tags. Clicking a motor opens a faceplate popup with Start/Stop.

Platforms
win · Windows
Applications
FactoryTalk View
Interfaces
desk · Desktop GUI
GUI need · task setting
G3 · GUI-only
GUI need · ordinary access
G3 · GUI-only
Interaction primitives
drag · Drag & drop click · Point & click type · Text & forms
Work product
WP08 · App/system state
Conditions
licensed · Licensed pro app
Proposed difficulty
4 / 5

Proposed verifier

Exported display XML: 4 global object references with parameter substitution; .par files contents; grader runs SE client automation: forcing M203 fault shows red only on M203; popup Start writes M203 command tag. FactoryTalk View VBA and the XML import wizards are disabled for the agent; display, .par and alarm files written by any process other than FactoryTalk View Studio are flagged by a file audit log.

Proposed partial credit

25% global object; 25% parameter files; 30% runtime animation; 20% popup commands

R07.07.02.02-T08 Add role-based navigation and security codes on a FactoryTalk ME terminal

Original instruction

In FactoryTalk View ME application fixtures/filler.med add a navigation bar on all displays linking 6 displays, assign security codes so Operators see Main/Alarms/Trends, Maintenance additionally Diagnostics/IO, Admin all, configure users per input/users.csv, and create a runtime .mer. Test in Test Application mode.

Platforms
win · Windows
Applications
FactoryTalk View
Interfaces
desk · Desktop GUI
GUI need · task setting
G3 · GUI-only
GUI need · ordinary access
G3 · GUI-only
Interaction primitives
click · Point & click drag · Drag & drop type · Text & forms
Work product
WP08 · App/system state
Conditions
licensed · Licensed pro app
Proposed difficulty
3 / 5

Proposed verifier

Exported XML: nav buttons on all displays; display security codes; users/groups; grader runtime test logs in as each role: allowed/blocked displays match matrix; .mer built. FactoryTalk View VBA and the XML import wizards are disabled for the agent; display, .par and alarm files written by any process other than FactoryTalk View Studio are flagged by a file audit log.

Proposed partial credit

25% navigation; 35% security matrix; 25% users; 15% runtime build

R07.07.02.02-T09 Restyle a legacy screen to ISA-101 high-performance HMI conventions

Original instruction

Ignition Perspective view Legacy/Boiler uses saturated colors, 3D pipes and blinking. Restyle it per docs/hp_hmi_style.pdf: grayscale background/equipment, color only for abnormal/alarm states (priority palette given), analog indicators with normal-range bands for 5 key variables, no animation except alarms. Keep all bindings.

Platforms
win · Windows mac · macOS lin · Linux
Applications
Ignition
Interfaces
desk · Desktop GUI
GUI need · task setting
G2 · GUI-essential
GUI need · ordinary access
G2 · GUI-essential
Interaction primitives
click · Point & click vis · Visual judgment drag · Drag & drop
Work product
WP08 · App/system state
Conditions
licensed · Licensed pro app
Proposed difficulty
4 / 5

Proposed verifier

Screenshot in normal state: ≥95% pixels within grayscale (chroma <8); in seeded alarm state only alarm palette colors appear on affected items; 5 range-band indicators bound to the right tags; all original bindings preserved (diff of binding paths). Designer Script Console, gateway API tokens and gateway file access are withheld from the agent; resources must be saved from a Designer session, and the gateway audit log records the actor.

Proposed partial credit

35% grayscale normal state; 25% alarm coloring; 25% range indicators; 15% bindings preserved

R07.07.02.02-T10 Recreate an area P&ID as a live Perspective screen from an image

Original instruction

Reproduce input/pid_area3.png (12 equipment items, 9 valves, 6 instruments) as Perspective view Area3/Process using the Ignition symbol library and pipes, bind each item to the tags in input/area3_tags.csv (status, value, valve position), and add click-to-open faceplates for the 9 valves.

Platforms
win · Windows mac · macOS lin · Linux
Applications
Ignition
Interfaces
desk · Desktop GUI
GUI need · task setting
G2 · GUI-essential
GUI need · ordinary access
G2 · GUI-essential
Interaction primitives
drag · Drag & drop geom · Precise geometry vis · Visual judgment
Work product
WP08 · App/system state
Conditions
licensed · Licensed pro app long · Long-horizon
Proposed difficulty
5 / 5

Proposed verifier

view.json: 27 bound components with correct tag paths; relative positions match P&ID topology (graph of pipe connections equals reference); runtime test: forcing tags animates the right symbols; 9 faceplates open with correct tag parameters. Designer Script Console, gateway API tokens and gateway file access are withheld from the agent; resources must be saved from a Designer session, and the gateway audit log records the actor.

Proposed partial credit

25% components & symbols; 25% bindings; 25% pipe topology; 25% faceplates

R07.07.02.02-T11 Show the last 50 alarm journal events in a Perspective table with filters

Original instruction

Configure alarm journal 'Journal' (sandbox DB) on the Ignition gateway, then add a Perspective Alarm Journal Table on view Alarms/History showing the last 50 events from it, with columns time, display path, priority, event state, and a dropdown filtering by area (Area1/Area2/Area3).

Platforms
win · Windows mac · macOS lin · Linux
Applications
Ignition
Interfaces
desk · Desktop GUI brow · Browser
GUI need · task setting
G2 · GUI-essential
GUI need · ordinary access
G2 · GUI-essential
Interaction primitives
click · Point & click drag · Drag & drop type · Text & forms
Work product
WP08 · App/system state
Conditions
licensed · Licensed pro app
Proposed difficulty
3 / 5

Proposed verifier

Gateway config has journal; grader generates 60 events then loads session: table shows 50 newest with the 4 columns; selecting Area2 shows only Area2 events. Designer Script Console, gateway API tokens and gateway file access are withheld from the agent; resources must be saved from a Designer session, and the gateway audit log records the actor.

Proposed partial credit

25% journal configured; 35% table content; 25% filter works; 15% columns

R07.07.02.02-T12 Configure user roles and role-based control visibility in WinCC Unified

Original instruction

In fixtures/dosing_unified.ap19 create roles Operator, Shift Lead, Engineer with function rights per input/rights_matrix.xlsx, users for each, and make the 'Setpoint' and 'Bypass interlock' controls on screen 'Dosing' operable only by the allowed roles (others see them disabled). Compile and test in simulation.

Platforms
win · Windows
Applications
WinCC
Interfaces
desk · Desktop GUI
GUI need · task setting
G3 · GUI-only
GUI need · ordinary access
G2 · GUI-essential
Interaction primitives
click · Point & click type · Text & forms
Work product
WP08 · App/system state
Conditions
licensed · Licensed pro app
Proposed difficulty
3 / 5

Proposed verifier

Openness/UMC export: roles/rights match matrix; screen item authorizations set; grader runtime logs in as each user: allowed controls operable, others disabled (DOM check in Unified browser runtime). TIA Portal Openness is denied to the agent (its Windows user is not in the 'Siemens TIA Openness' group; exports are grader-only), so the project must be edited in the TIA Portal UI.

Proposed partial credit

35% roles & rights; 15% users; 50% runtime authorization

R07.07.02.02-T13 Make a Perspective view responsive for phone and desktop with breakpoints

Original instruction

Convert Ignition view Mobile/LiftStation into a breakpoint container: below 600 px show a single-column card layout with large touch buttons (≥48 px) for Pump1/Pump2 Start/Stop and wet-well level; above 600 px show the existing desktop layout. Both must keep the same bindings.

Platforms
win · Windows mac · macOS lin · Linux
Applications
Ignition
Interfaces
desk · Desktop GUI
GUI need · task setting
G2 · GUI-essential
GUI need · ordinary access
G2 · GUI-essential
Interaction primitives
drag · Drag & drop click · Point & click vis · Visual judgment
Work product
WP08 · App/system state
Conditions
licensed · Licensed pro app
Proposed difficulty
4 / 5

Proposed verifier

Playwright sessions at 390×844 and 1440×900: correct layout per width; touch targets ≥48 px; tapping Start writes the right tag; level value matches tag in both layouts. Designer Script Console, gateway API tokens and gateway file access are withheld from the agent; resources must be saved from a Designer session, and the gateway audit log records the actor.

Proposed partial credit

30% breakpoint structure; 25% mobile layout & touch targets; 30% writes/bindings in both; 15% desktop unchanged

R07.07.02.02-T14 Control pair of T01: author the tank view as project JSON and push it

Original instruction

Control pair of T01. Without the Designer, author the Tanks/Tank1 Perspective view (view.json), the tag alarm config and the write-limit logic as project files, then load them to the sandbox gateway via the project directory and a scan, and the tag JSON via the gateway import endpoint.

Platforms
lin · Linux mac · macOS
Applications
Ignition
Interfaces
term · Terminal api · API/SDK
GUI need · task setting
CL · CLI-sufficient
GUI need · ordinary access
CL · CLI-sufficient
Interaction primitives
code · Code & commands
Work product
WP08 · App/system state
Conditions
licensed · Licensed pro app
Proposed difficulty
3 / 5

Proposed verifier

Same runtime checks as T01 (level, alarm indicator, SP write/limits). Compared with T01 for GUI vs file modality.

Proposed partial credit

30% level binding; 20% alarm; 35% setpoint write; 15% layout

R07.07.02.02-T15 Set up tag-based alarms in a FactoryTalk Alarms & Events server

Original instruction

In FactoryTalk View SE (sandbox) add a Tag Alarm and Event Server, define 12 digital/level alarms from input/ae_list.xlsx with severity, messages and associated tags, add an alarm summary and banner to display 'Header', and verify acknowledge and shelve work in the SE client.

Platforms
win · Windows
Applications
FactoryTalk View
Interfaces
desk · Desktop GUI
GUI need · task setting
G3 · GUI-only
GUI need · ordinary access
G2 · GUI-essential
Interaction primitives
click · Point & click type · Text & forms drag · Drag & drop
Work product
WP08 · App/system state
Conditions
licensed · Licensed pro app
Proposed difficulty
4 / 5

Proposed verifier

Exported alarm XML: 12 alarms with types/limits/severity/messages per list; grader toggles source tags: alarms appear in summary with severity; ack and shelve recorded in A&E history DB. FactoryTalk View VBA and the XML import wizards are disabled for the agent; display, .par and alarm files written by any process other than FactoryTalk View Studio are flagged by a file audit log.

Proposed partial credit

40% alarm definitions; 20% summary/banner; 25% runtime appearance; 15% ack/shelve

R07.07.02.02-T16 Build a docked navigation menu across five Perspective pages

Original instruction

In Ignition project 'WaterPlant' create page configuration for /overview, /tanks, /pumps, /alarms, /trends mapped to existing views, and a docked left menu (Menu Tree component) linking them, highlighting the active page, visible on all pages.

Platforms
win · Windows mac · macOS lin · Linux
Applications
Ignition
Interfaces
desk · Desktop GUI
GUI need · task setting
G2 · GUI-essential
GUI need · ordinary access
G2 · GUI-essential
Interaction primitives
click · Point & click type · Text & forms drag · Drag & drop
Work product
WP08 · App/system state
Conditions
licensed · Licensed pro app
Proposed difficulty
2 / 5

Proposed verifier

Page config JSON: 5 URLs to views; shared docked view on all pages; Playwright clicks each menu item → correct URL/view, active item highlighted. Designer Script Console, gateway API tokens and gateway file access are withheld from the agent; resources must be saved from a Designer session, and the gateway audit log records the actor.

Proposed partial credit

35% page config; 35% dock on all pages; 30% navigation test

R07.07.02.02-T17 Configure logging tags and a trend view in WinCC with archive settings

Original instruction

In fixtures/hvac_comfort.ap19 (WinCC Comfort) create data log 'HVAC_Log' (circular, 50,000 entries), log tags for supply temp, return temp and fan speed (cyclic 5 s; fan speed on change), and a trend view on screen 'Trends' showing 2 h with these logged values. Simulate and confirm entries accumulate.

Platforms
win · Windows
Applications
WinCC
Interfaces
desk · Desktop GUI
GUI need · task setting
G3 · GUI-only
GUI need · ordinary access
G2 · GUI-essential
Interaction primitives
click · Point & click type · Text & forms drag · Drag & drop
Work product
WP08 · App/system state
Conditions
licensed · Licensed pro app
Proposed difficulty
3 / 5

Proposed verifier

Openness export: data log settings; 3 logging tags with modes/cycles; trend view pens; runtime simulation log file contains entries for all 3 at expected rates. TIA Portal Openness is denied to the agent (its Windows user is not in the 'Siemens TIA Openness' group; exports are grader-only), so the project must be edited in the TIA Portal UI.

Proposed partial credit

30% data log; 30% logging tags; 25% trend view; 15% runtime data

R07.07.02.02-T18 Map pump state codes to text and colors with expression bindings and transforms

Original instruction

In Ignition view Pumps/P101 bind a label to [default]P101/State (0-5) via a map transform to text (Stopped, Starting, Running, Stopping, Fault, Maintenance) and a style binding to colors per docs/state_colors.csv; add an expression binding showing runtime as 'hh:mm' from P101/RuntimeSec.

Platforms
win · Windows mac · macOS lin · Linux
Applications
Ignition
Interfaces
desk · Desktop GUI
GUI need · task setting
G2 · GUI-essential
GUI need · ordinary access
G2 · GUI-essential
Interaction primitives
click · Point & click type · Text & forms
Work product
WP08 · App/system state
Conditions
licensed · Licensed pro app
Proposed difficulty
2 / 5

Proposed verifier

Grader sets State 0-5 and RuntimeSec values: label text/background match mapping; hh:mm correct (e.g., 3725 → 01:02). Designer Script Console, gateway API tokens and gateway file access are withheld from the agent; resources must be saved from a Designer session, and the gateway audit log records the actor.

Proposed partial credit

40% text mapping; 30% colors; 30% runtime expression

R07.07.02.02-T19 Build a valve faceplate popup with interlock display and confirmed writes

Original instruction

Create Ignition Perspective popup view Faceplates/Valve with a view parameter tagPath: shows position, mode (Auto/Manual), active interlocks list (from member Interlocks bitmask decoded with names), Open/Close buttons enabled only in Manual with no interlock, and a confirmation dialog before writing. Open it from XV-301 on Area3 screen.

Platforms
win · Windows mac · macOS lin · Linux
Applications
Ignition
Interfaces
desk · Desktop GUI
GUI need · task setting
G2 · GUI-essential
GUI need · ordinary access
G3 · GUI-only
Interaction primitives
drag · Drag & drop click · Point & click type · Text & forms
Work product
WP08 · App/system state
Conditions
licensed · Licensed pro app
Proposed difficulty
3 / 5

Proposed verifier

Runtime tests: in Auto buttons disabled; interlock bit 2 set → listed name and buttons disabled; Manual no interlock → write only after confirm; parameterized (works for XV-302 via param). Designer Script Console, gateway API tokens and gateway file access are withheld from the agent; resources must be saved from a Designer session, and the gateway audit log records the actor.

Proposed partial credit

20% parameterized popup; 25% interlock decoding; 30% button enable logic; 25% confirmation write

R07.07.02.02-T20 Configure state-based alarm suppression and operator shelving

Original instruction

For Unit 2 in Ignition, suppress (not just hide) all 40 process alarms in [default]Unit2 while Unit2/Mode is 'Offline' or 'Startup' (first 10 min), keep safety alarms (folder Unit2/Safety) unsuppressed, and add a Perspective alarm status table allowing shelving for 15/30/60 min with a required reason. Document the logic in out/suppression.md.

Platforms
win · Windows mac · macOS lin · Linux
Applications
Ignition
Interfaces
desk · Desktop GUI
GUI need · task setting
G2 · GUI-essential
GUI need · ordinary access
G2 · GUI-essential
Interaction primitives
click · Point & click type · Text & forms drag · Drag & drop
Work product
WP08 · App/system state
Conditions
licensed · Licensed pro app long · Long-horizon
Proposed difficulty
5 / 5

Proposed verifier

Grader drives Mode and alarm conditions: process alarms do not activate when suppressed and do after 10 min Startup; safety alarms always activate; shelving via UI only with reason, auto-unshelves at the chosen time. Designer Script Console, gateway API tokens and gateway file access are withheld from the agent; resources must be saved from a Designer session, and the gateway audit log records the actor.

Proposed partial credit

40% suppression logic; 20% safety excluded; 30% shelving UI; 10% documentation